Product Introduction
wecoost fan coil products are divided into concealed type and surface-mounted type, where the concealed type incudes 2-rowcoil,3-row coil,3+1-row coil (4 tubes) and DC brushless motor, and the surface-mounted type includes horizontal-vertcalsurface-mounted type,cassette four-blow type, and cassette two-blow type, etc. All these products are made by high -qualityaccessories, thus featuring by advanced structure, efficient performance, low consumption and low noise, beautiful appearance,and easy to maintain.
Horizontal Concealed Series
· Low Noise
The design has selected high-quality galvanized steel rotor, which transmits air in streamline form through strict dynamic andstatic balanced adjustment, so as to reduce the production of vortex airflow and airflow friction noise as well as ensure stableand quite unit operation.
· Wide Application Scope
To achieve the best air-conditioning effect,selectthe unit of different air volumes and enthalpydifferences according to different cold loads anddifferent using requirements. DunAn low-noisehorizontal concealed fan coil unit is speciallydesigned to meet such requirements. This seriesproduct includes 2-row coil, 3-row coil, and DC type,which can maximally meet users' requirements andcreate the most comfort air-conditioning system.
Horizontal Concealed Series
·Various Accessories
According to the requirements of different air-conditioning systems,the unit provide stainlesssteel or elongated water plate, various return airbellows,FPT rubber joint,water filter,andcontrollers with various functions for selection.The unit adopts ultra-thin design,with height ofonly 235 mm,can maximally meet the siteinstallation requirements of users.
· Reliability
1.The thermal insulation layer thickness of wideone-time forming condensate water plate is 7mm, completely preventing from condensation;2. High-quality oil bearing is selected,withoutrequiring to fill oil.
3. Hydrophilic aluminum fin,preventing fromcorrosion and mold, reducing wateraccumulation and improving the heat exchangeefficiency.
Horizontal Concealed Series
Model |
FP-34WA |
FP-51WA |
FP-68WA |
FP-85WA |
FP-102WA |
FP-136WA |
FP-170WA |
FP-204WA |
FP-238WA |
A |
445 |
575 |
675 |
735 |
835 |
1215 |
1265 |
1515 |
1755 |
B |
472 |
602 |
702 |
762 |
862 |
1242 |
1292 |
1542 |
1782 |
C |
Standard water plate |
678 |
808 |
908 |
968 |
1068 |
1448 |
1498 |
1748 |
1988 |
Elongated water plate |
928 |
1058 |
1158 |
1218 |
1318 |
1698 |
1748 |
1998 |
2238 |
D |
Standard water plate |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
Elongated water plate |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
E |
48 |
48 |
48 |
48 |
48 |
48 |
48 |
48 |
48 |
Horizontal Concealed Series
1.High-efficiency dust removal: Purification efficiency of PM2.5 particles is ≥91%;
2.Comprehensive sterilization:Killing rate of various viruses is ≥ 99%; removal rate of harmful rate is ≥ 95%;
3.Free selection: Users can choose dust removal type(JDX), sterilization type (CHX) and composite type (dust removal +sterilization)(FHX) according to requirements;
4.Long-lasting energy saving: Small air resistance (≤20Pa), with the service life of more than 10 years;
5. Safe and simple: Single functional section, can be installed at the return air inlet of fan coil or in the return air ductindependently.
Surface-mounted Series
Note:
Elegant appearance: Beautiful view
Saving space: Maximum thickness of 250mm
The standard control mode is three-speed switch control,with remote control and wire control optional
The vertical surface mounted type has up-air outlet type only
The horizontal surface mounted type has down-return air and front air outlet type only
Judgment criteria for left and right type of unit: Facing the return air inlet,if the connecting pipe is on the left, it is left type; other wise, it is right type;
Model |
FP-51 |
FP-68 |
FP-85 |
FP-102 |
FP-136 |
FP-170 |
FP-204 |
Rated air volume (mh) |
H |
510 |
680 |
850 |
1020 |
1360 |
1700 |
2040 |
M |
384 |
510 |
638 |
765 |
1020 |
1275 |
1530 |
L |
258 |
340 |
425 |
510 |
680 |
850 |
1020 |
Refrigerating capacity (W) |
H |
2680 |
3640 |
4480 |
5350 |
7180 |
8950 |
10600 |
M |
2270 |
3020 |
3770 |
4530 |
6040 |
7515 |
8350 |
L |
1650 |
2170 |
2710 |
3250 |
4340 |
5420 |
6050 |
Heating capacity (W) |
H |
4050 |
5400 |
6750 |
8100 |
10800 |
13500 |
16200 |
M |
3240 |
4290 |
5370 |
6430 |
8580 |
10720 |
13380 |
L |
2260 |
3000 |
3710 |
4450 |
5950 |
7450 |
9580 |
Power (W) |
H |
51 |
62 |
71 |
94 |
124 |
152 |
188 |
Noise (dB(A)) |
H |
39 |
41 |
43 |
45 |
46 |
48 |
50 |
Power supply |
220-240V/1P/50Hz |
Coll working pressure |
1.6MPa |
Inlet/outlet water pipe joint |
Rc3/4 (internal thread) |
Condensate water Joint |
cp20mm |
Water ftow (Kg /h) |
H |
520 |
700 |
876 |
1050 |
1400 |
1750 |
1990 |
Water resistance (Kpa) |
H |
5.9 |
11.9 |
19.7 |
31.9 |
37.8 |
24.2 |
29.4 |
Weight (Kg) |
19 |
21 |
22 |
27 |
39 |
47 |
49 |
Cassette Double-blow Fan Coil
Note:
Km2 indicates cassette double-blow type unit;
Suitable for long and narrow space,such as corridor or long andnarrow living room or dining room; two-way air outlet design,guaranteeing uniform air flow;
No left/right type division of unit;
Equipped with condensate water lift pump (with lift of 700 mm) andremote control.
Model |
FP-34KM4 |
FP-51KM4 |
FP-68KM4 |
FP-85KM4 |
FP-102KM4 |
FP-136KM4 |
FP-170KM4 |
FP-204KM4 |
FP-238KM4 |
Rated air volume m' /h |
340 |
510 |
680 |
850 |
1020 |
1360 |
1700 |
2040 |
2380 |
Refrigeatin g capacity (W) |
1800 |
2700 |
3600 |
4500 |
5400 |
7200 |
9000 |
10800 |
12150 |
Heating capacity (W) |
2 7 00 |
4050 |
5400 |
6750 |
8100 |
10800 |
13500 |
16200 |
17500 |
Piping size |
Inlet/outlet water pipe |
Rc3 /4(DN20) |
Condensate pipe |
<ll20 |
W a t er flow (kg/h) |
350 |
520 |
700 |
860 |
1050 |
1400 |
1750 |
1990 |
2320 |
Wateres1stance kpa |
30 |
30 |
30 |
30 |
40 |
40 |
40 |
40 |
50 |
Input power W |
37 |
52 |
62 |
76 |
96 |
134 |
152 |
189 |
228 |
Noise dB (A) |
3 7 |
,,;;39 |
41 |
43 |
,s;:;45 |
46 |
48 |
5 0 |
52 |
Connection type |
Internal thread connection |
Power supply |
|
|
|
1/N/PE/AC |
220V |
50HZ |
|
|
|
Unit net weight (kg) |
Type 290 |
23 |
23 |
23 |
34 |
34 |
34 |
48 |
48 |
48 |
Type 390 |
23 |
23 |
23 |
34 |
34 |
34 |
48 |
48 |
48 |
Working pessure (Mpa) |
16 |
Overall dimensions |
A*B |
650 *650 |
650 *650 |
650 *650 |
850 *850 |
850 *850 |
850 *850 |
1050 *1050 |
1050 *1050 |
1050 *1050 |
L*S |
570 *570 |
570 *570 |
570 *570 |
730 *730 |
730 *730 |
730 *730 |
930 *930 |
930 *930 |
930 *930 |
K*H |
280 *616 |
280 *616 |
280 *616 |
440*77 6 |
440 *77 6 |
440 *77 6 |
640 *976 |
640 *976 |
640 *976 |
Optional Accessories
- The accurate address of the building
- The application of the building
- The size of the building, such as the height of each floor?
- The drawing of the building
- The environment condition of the building, such as highest temperature in summer
- The working condition of the outdoor units
- The function of each room
- Which rooms need indoor units
- Is it an old building or new building
- If it is still not decorated
- Which kind of indoor units do you prefer according to the catalog
- What is the local power supply for your building
Customisation process